FCL/S x.6.1.1 | 2CDC508116D0203 55
3.2.2.4
Parameter window
B: Output
Note
All of the following descriptions and operating options apply to both the FCL/S 1.6.1.1 1-fold Blower
Actuator and the FCL/S 2.6.1.1 2-fold Blower Actuator.
All settings for output B are made in the
B: Output
parameter window.
These explanations also apply to outputs C, D, E if the parameter
Outputs C, D, E
, p.20 is set to
Enable as switch actuators.
The explanations also apply for output F.
Outputs B…F must first be individually enabled in
Parameter window Enable outputs A...F
Reaction of output
Options:
Normally opened contact
Normally closed contact
This parameter sets whether the output operates as a
normally closed contact
or
normally open contact
.
Normally opened contact
: An ON telegram (1) closes the contact, and an OFF telegram (0) opens the
contact.
Normally closed contact
: An ON telegram (1) opens the contact, and an OFF telegram (0) closes the
contact.
Contact position
on bus voltage failure
Options:
Normally closed
Normally Open
Unchanged
This parameter determines the response of the output on bus voltage failure.
Normally closed
: The output is OFF.
Normally open
: The output is ON.
Unchanged
: The output retains the last state before bus voltage failure.