![ABB FSPS-21 User Manual Download Page 48](http://html.mh-extra.com/html/abb/fsps-21/fsps-21_user-manual_2729048.webp)
tables below and must be checked first and adjusted where necessary. You can adjust the
parameters via a drive control panel or a PC tool.
•
The new parameter settings take effect only when you power up the module the next
time or when you activate the fieldbus adapter refresh parameter.
FSPS-21 configuration parameters – group A (group 1)
Note:
The actual parameter group number depends on the drive type. Group A (group 1)
corresponds to:
•
parameter group 51 in ACS380 and ACS580.
•
parameter group 51 in ACS880 if the adapter is installed as fieldbus adapter A or group
54 if the adapter is installed as fieldbus adapter B.
Default
Description
Name/Value
No.
133
= PROFIsafe
Read-only.
Shows the fieldbus adapter type as detec-
ted by the drive. The value cannot be adjusted by the
user.
If the value is 0 = None, the communication between
the drive and the module has not been established.
FBA type
01
11
= PNIO ABB Pro
Selects the application protocol and communication
profile for the network connection.
The selections available for PROFINET IO communic-
ation are listed below.
Protocol.Profile
02
PROFINET IO protocol: PROFIdrive profile
10
= PNIO Pdrive
PROFINET IO protocol: ABB Drives profile
11
= PNIO ABB Pro
PROFINET IO protocol: Transparent 16-bit profile
12
= PNIO T16
PROFINET IO protocol: Transparent 32-bit profile
13
= PNIO T32
PROFINET IO protocol: PROFIdrive positioning mode
14
= PNIO PdriveM
0
= Auto
Sets the bit rate for the Ethernet interface.
Commrate
03
Auto-negotiate
0
= Auto
100 Mbps, full duplex
1
= 100 Mbps FD
100 Mbps, half duplex
2
= 100 Mbps HD
10 Mbps, full duplex
3
= 10 Mbps FD
10 Mbps, half duplex
4
= 10 Mbps HD
48 PROFINET IO – Start-up
Summary of Contents for FSPS-21
Page 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Page 2: ......
Page 4: ......
Page 11: ...Further information Table of contents 11 ...
Page 12: ...12 ...
Page 26: ...26 ...
Page 38: ...38 ...
Page 42: ...42 ...
Page 46: ...46 ...
Page 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Page 86: ...86 ...
Page 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Page 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Page 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Page 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Page 178: ... starting the system does not cause any danger 178 Start up ...
Page 186: ...186 ...
Page 192: ...192 ...
Page 200: ...200 ...
Page 208: ...208 ...
Page 212: ......