![ABB FSO-21 User Manual Download Page 522](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728522.webp)
522 Technical data
Basic safety data
The FSO-21 module is a type B safety component as defined in IEC 61508-2.
The FSO-21 data related to safety standards IEC 61508, EN/IEC 61800-5-2,
EN ISO 13849-1, IEC 61511, and EN/IEC 62061 is listed below for the different
subsystems within the FSO module.
The maximum useful mission time (
T
m
) for the FSO module is 20 years. After 20
years, the module must be replaced.
The given safety data is applicable with these proof test intervals:
• T1 = 20 years (high demand and continuous mode of operation)
• T1 = 2, 5, or 20 years (low demand mode of operation).
Make sure that the proof test is performed within this time (see also section
on page
).
EN/IEC 61508
EN ISO 13849-1
EN/IEC 62061
SIL
up to 3
PL
up to e
SIL
3
3AXD10001287182 C
1-ch. DI,
pulses
2-ch. DI,
pulses
1-ch. DI,
no pulses
2-ch. DI,
no pulses
Logic
PROFI-
safe
1)
SIL
3
3
2
3
3
3
PL
d
e
c
e
e
e
PFH (1/h)
(T1 = 20 a)
1.1E-10
5.5E-12
1.1E-08
2.9E-11
1.1E-11
1.0E-09
PFD
avg
(T1 = 2 a)
5.8E-08
5.9E-08 5.7E-06
6.7E-07
9.9E-08 8.8E-06
PFD
avg
(T1 = 5 a)
1.4E-07
1.5E-07 1.4E-05
1.7E-06
2.5E-07
2.2E-05
PFD
avg
(T1 = 20 a)
5.8E-07
5.9E-07
5.8E-05
6.7E-06
9.9E-07
8.8E-05
MTTF
D
(a)
10747
10431
10628
10738
11290
114155
HFT
0
1
0
1
1
-
Cat.
2
3
1
3
3
4
SFF (%)
99.7
99.7
73.5
98.6
99.0
99.0
DC (%)
99.0
99.0
1.4
94.6
96.7
99.0
3AXD10001287182 C
1) We assume conservatively that PFH =
λ
d = 1, FIT = 1e-9 1/h,
MTTF
D
= 1/
λ
d = 1/(1e-9 1/h) = 1e9 h = 114155 a. Based on the BGIA Report 2/2008e: Functional Safety of
Machine Controls – Application of EN ISO 13849, ch. 6.2.17.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...