364 Configuration
How to configure SLSn with ramp monitoring
Example:
The figure below shows an example of the SLS2 function with ramp
monitoring set-up:
• SLS2 function activated (
=
Version 1
)
• monitored deceleration ramp
SLS activation monitoring method
Ramp
)
• deceleration ramp and monitoring limits according SAR1 parameters (see section
on page
• automatic acknowledgement (
=
Automatic
)
• redundant SLS activation button connected to input
=
DI X113:2 & X114:2
)
• single output connected (
=
DO X114:7
)
• positive limits: SLS 1200.0 rpm, trip limit 1320.0 rpm
=
1200 rpm,
=
1320 rpm
).
• negative limits: SLS -900.0 rpm, trip limit -1020.0 rpm
=
-900 rpm,
-1020 rpm
).
• See also section
on page
.
Note
: The difference between the SLS limit and the corresponding SLS trip limit must
be at least 0.1 rpm.
Note
: If you also use the SMS function, the SLS trip limits positive and negative must
be below the speed defined by parameter
and above the speed
defined by parameter
, respectively.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...