PROFIsafe 283
6. To check the Device number of the FENA module, select the
General
tab.
Diagnostic messages related to F-Parameters
The diagnostics messages in this table are caused by problems in the
F-Parameter processing that takes place only when the controller station sends the
F-Parameters to FB module. This happens normally only when the controller station
starts up the PROFINET communication with the FB module.
Value
(hex)
Description
Notes
64
(0x0040)
Mismatch of safety destination
address (F_Dest_Add).
F_Dest_Add did not match the value
configured in the safety parameters
(
65
(0x0041)
Safety destination address is not valid
(F_Dest_Add).
F_Dest_Add of 0 or FFFFh is not allowed.
A valid F_Dest_Add is within range
1...65534.
66
(0x0042)
Safety source address is not valid
(F_Source_Add).
F_Source_Add of 0 or FFFFh is not
allowed.
A valid F_Source_Add is within range
1...65534.
67
(0x0043)
Safety watchdog time value is 0 ms
(F_WD_Time).
Watchdog time 0 ms is not allowed.
A valid F_WD_Time is within range
1...65535.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...