56 Safety functions
STO function
The operation of the STO function when the SBC is not used is described in the time
diagram and table below. For configuration, see section
on
page
A
): Time from the STO activation to the moment
when the safety function is completed and the STO completed indication (parameter
) goes on. You must set this to the estimated time in which the motor coasts to a
stop from the maximum speed.
B
Restart delay after STO (parameter
): Time from the STO activation to the
moment when the acknowledgment becomes allowed. With this parameter, you can
allow a restart of the drive before the motor has stopped (fly-start). You can use this
feature only in certain applications. This parameter is relevant only when an external
request activates the STO function.
Step
Description
1
The STO request is received (for example, from the I/O). The FSO activates the drive
STO function and starts counters for times A and B.
2
After time B has elapsed, the acknowledgement becomes allowed as soon as the
STO request has been removed (step 4).
Note
: If an SSE or SS1 request is received while the STO function is active, the STO
function must be completed before the acknowledgement is allowed.
3
After time A has elapsed, the FSO module defines the motor as stopped and the STO
completed indication goes on.
4
The STO request is removed.
5
After the acknowledgement, the STO function is deactivated and the indications go
off.
Drive STO state
& indication
4
STO request
Motor speed
Time
A
5
3
STO completed
indication
1
B
2
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...