FSM4000
ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
85
Submenu / parameter
Value range
Remark
Submenu
In this menu you can set minimum and maximum values for
each measurement value. Depending on the selected
configuration, you can select for no message, a warning, or an
error message to be displayed, if the value falls below or
exceeds this threshold.
Alarm Settings
Submenu
Set the time-out limits and alarm behavior for values over or
under the coil AC voltage.
Alarm Coil Voltage
Min. value
0 ... 150
Lower range limit for alarm
1.0 V
Max. value
0 ... 150
Upper range limit for alarm
150 V
Message
Off, warning, error
Defines the alarm behavior
Off
Submenu
Set the time-out limits and alarm behavior for values over or
under the coil AC.
Alarm Coil Current
Min. value
0 ... 500
Lower range limit for alarm.
20.0 mA
Max. value
0 ... 500
Upper range limit for alarm.
500.0 mA
Message
Off, warning, error
Defines the alarm behavior.
Off