Parameterization
38 - EN
FSM4000
D184B141U02
6.3
Easy Set-up: For uncomplicated configuration
The Easy Set-up function enables users to configure the transmitter for quick and convenient
startup. For additional information about configuration options, see the chapter
"Parameterization"
.
G00563
EASY SETUP
N
S
N
S
N
S
FSM4000
DATA
STEP
ENTER
1
2
3
C/CE
Note!
Parameters can be changed
only when the Program protection
is turned off.
No = STEP
Jump to menu level
Yes = ENTER
Language
English
Unit Qmax
l/s
Unit totalizer
m3
Qmax
50.000 l/s
Damping 1 Tau
0.22 sek
Display mode
4 small
Display 1st line
Q [Unit]
Display 2nd line
Display 4th line
Display 3rd line
Within “Easy Set-up”,
call up the next parameter
using the C/CE key.
Change the parameter
using the
“Enter” function.
[m/s]
Q
Pulse width
0.1000 ms
Pulse factor
1/m3
lout High Alarm
23.000 mA
lout Low Alarm
3.6 mA
Iout at Alarm
High Alarm
Totalizer
V
→
Totalizer
R
←
Press any key in the
process display, then use
STEP or DATA to scroll
to the “Easy Set-up“ menu.
“Easy Set-up“ finished.
Jump back to the process display
or use STEP to go to the menu level.
1 Magnet sensor C/CE
2 Magnet sensor
3 Magnet sensor STEP
DATA (> 1s = ENTER)
Fig. 40