Start-up 79
10. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Parameter setting examples – ACS880 and ACS880-
M04
Speed control using the PROFIdrive communication profile
with PPO Type 2
This example shows how to configure a basic speed control
application that uses the PROFIdrive profile.
The start/stop commands and reference are according to the
PROFIdrive profile, speed control mode. For more information, see
the PROFIdrive state machine on page
The reference value ±16384 (4000h) corresponds to parameter
46.01 Speed scaling
in the forward and reverse directions.
The table below gives the recommended drive parameter settings.
Direction
PZD1
PZD2
PZD3 PZD4 PZD5 PZD6
Out
Control word
Speed
reference
Constant
speed 1
Constant
speed 2
In
Status word
Speed actual
value
Motor current
DC voltage
Drive parameter
Setting for
ACS880 drives
Description
50.01 FBA A enable
1
= Option slot 1
Enables communication
between the drive and the
fieldbus adapter A module (if
adapter is in slot 1).
50.04 FBA A ref1 type
4
= Speed
Selects the fieldbus A
reference 1 type and scaling.
50.07 FBA A actual 1
type
4
= Speed
Selects the actual value type
and scaling according to the
currently active Ref1 mode
defined in parameter
50.04
.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...