Start-up 75
Parameter setting examples – ACS850 and ACQ810
Speed control using the PROFIdrive communication profile
with PPO Type 2
This example shows how to configure a basic speed control
application that uses the PROFIdrive profile. In addition, some
application-specific data is added to the communication.
The start/stop commands and reference are according to the
PROFIdrive profile, speed control mode. For more information, see
the PROFIdrive state machine on page
The reference value ±16384 (4000h) corresponds to parameter
19.01 Speed scaling
in the forward and reverse directions.
The table below gives the recommended drive parameter settings.
Direction PZD1
PZD2
PZD3
PZD4
PZD5
PZD6
Out
Control
word
Speed
reference
Constant speed
1
1)
Constant speed
2
1)
In
Status
word
Speed
actual value
Power
1)
DC bus voltage
1)
1)
Example
Drive parameter
Setting for
ACS850/
ACQ810 drives
Description
50.01 Fba enable
Enable
Enables communication
between the drive and the
fieldbus adapter module.
50.02 Comm loss
func
Fault
Enables fieldbus
communication fault
monitoring.
50.03 Comm loss t
out
3.0 s
Defines the fieldbus
communication break
supervision time.
50.04 Fb ref1
modesel
Speed
Selects the fieldbus reference 1
scaling.
Summary of Contents for FPBA-01 PROFIBUS DP
Page 4: ......
Page 10: ...10 Table of contents Document library on the Internet 195 ...
Page 20: ...20 About the manual ...
Page 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Page 30: ...30 Mechanical installation ...
Page 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Page 98: ...98 Start up ...
Page 118: ...118 Communication profiles ...
Page 178: ...178 Diagnostics ...
Page 182: ...182 Technical data ...