Start-up 71
Starting up ACS380 drives
The ACS380 software automatically sets the relevant parameters
when the fieldbus adapter module is connected to the drive.
Automatic configuration is only minimum configuration, and you
can change these parameters later, e.g., Node address.
Parameter
General setting
20.01 Ext1 commands
Fieldbus A
20.03 Ext1 in1
Not selected
20.04 Ext1 in2
Not selected
22.11 Ext1 speed ref1
FB A ref1
22.22 Constant speed sel1
Not selected
22.23 Constant speed sel2
Not selected
23.11 Ramp sel selection
Acc/Dec time 1
28.11 Ext1 frequency ref1
FB A ref1
28.22 Constant frequency sel1
Not selected
28.23 Constant frequency sel2
Not selected
28.71 Freq ramp set sel
Acc/Dec time 1
31.11 Fault reset selection
DI1
50.01 FB A enable
Enable
50.02 FB A comm loss func
Fault
51.02 Node address
3
51.05 Profile
ABB Drives
52.01 FBA A data in1
SW 16 bit
52.02 FBA A data in 2
Act1 16 bit
53.01 FBA A data out1
CW 16 bit
53.02 FBA A data out2
Ref1 16 bit