30 Quick Installation Guide LD 810HSE Ex |
2PAA118721
Section 4 Specifications
Power supply
18 V DC ... 32 V DC; SELV/PELV supply mandatory
The 4 FF H1 channels' output current is 10 mA each.
Typical input current is 200 mA; maximum is 1 A (consider-
ing the rush-in current at switch-on).
FF-H1
4 FF-H1 channels, compliant with type 114 of the FF
physical layer profile.
Fieldbus voltage range is 9 V DC ... 32 V DC.
Preferred voltage is 24 V DC.
Ethernet
IEEE 802.3 100BASE-TX/10BASE-T
Minimum ambient
operating temperature
−40 °C
Storage temperature
−40 °C ... +85 °C
Relative humidity
10 % ... 95 % (non-condensing)
Altitude
Must not exceed 2,000 m
Location
Indoor use only and no direct sunlight.
Coating
Conformal Coating based on ANSI/ISA-S71.04 G3.
Safety standard
IEC/EN/UL 61010-1, “Safety requirements for electrical
equipment for measurement, control and laboratory use -
Part 1: General requirements” and
IEC/EN/UL 61010-2-201, “Safety requirements for electri-
cal equipment for measurement, control and laboratory
use - Part 2-201: Particular requirements for control
equipment” (both with CB scheme)
Ingress protection
IP20