Reset FMBT-21 web page password to default
You can reset the FMBT-21 web page password to factory default.
Note: The password can be reset only with local access to the drive.
1.
Disconnect all cable connections to FMBT-21.
The NET led should switch off.
2.
Write 0 (zero) to the parameter 26 under Group A (e.g. 51.26).
3.
Refresh the settings by selecting Refresh in parameter 27 (e.g. 51.27).
4.
Write 17989 to parameter 26 under Group A.
5.
Refresh the settings by selecting Refresh in parameter 27.
6.
Write 20033 to parameter 26 under Group A.
7.
Refresh the settings by selecting Refresh in parameter 27.
8.
Write 0 to parameter 26 under Group A.
FMBT-21 password is now reset to the default password. For information of default
password, see section
.
Enable web page access after it was disabled
You can enable the access to web pages with drive parameters.
1.
Disconnect all cable connections to FMBT-21.
The NET led should switch off.
2.
Write 0 (zero) to the parameter 26 under Group A (e.g. 51.26).
3.
Refresh the settings by selecting Refresh in parameter 27 (e.g. 51.27).
4.
Write 87 to parameter 26 under Group A.
5.
Refresh the settings by selecting Refresh in parameter 27.
6.
Write 17730 to parameter 26 under Group A.
7.
Refresh the settings by selecting Refresh in parameter 27.
8.
Write 0 to parameter 26 under Group A.
Appendix D - FMBT-21 configuration web pages 89
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...