Installation instruction

Shield connections in X51

Connect the shield wires of the encoder cable to terminal X51 (SHIELD).

Signal connections for TTL encoder

Note:

 Default voltages for TTL are +5.5 V or +24 V. To use +8 V operating voltage for the TTL encoder, remove the 

TTL jumpers from the FEN voltage selection, and assemble the voltage selection jumper to ABS +8 V. Connect the 

wire from FETA-01 ABS_VCC X42 (5) to TTL_VCC X41 (7).

FETA-board provides screw terminal block connection to the D-sub connectors of FEN-01, -11 or -21 encoder 

interface module. Terminal block X41 connects to the 9-pin D-sub connector of the FEN-module. Terminal blocks 

X32 and X42 connect to the 15-pin D-sub connector.
1.

Hang on the hooks (a) of the FETA-board to the FEN-module.

2. Swing the board down to engage the connectors (b).
3. Tighten the four screws (c), 0.5 N·m, to fix the board to the module.
4. Make the connections according to the connection tables.

1

2

3

a

b

c

To remove the FETA-board from the 

FEN-module, unscrew the four screws 

(c), then use a screwdriver to carefully 

lift the end of the board to disengage 

the connectors (b).

SHIELD

X42

X32

X41

Terminal 

X41 pin

1

2

3

4

5

6

7

8

9

Signal

A+

A-

B+

B-

Z+

Z-

TTL_VCC

TTL_COM

TTL_COM

OPTIONS FOR ABB DRIVES

FETA-01 adapter board

Installation guide