Communication profiles 93
Velocity mode
Basic mode to control the velocity of the drive with limits and ramp
functions.
Target velocity of CiA 402 Velocity mode
Target velocity is the required velocity of the application. The unit
of the target velocity is interpreted as rpm. 1 = 1 rpm.
Control effort of CiA 402 Velocity mode
Control effort is the actual velocity of the application. The unit of
the control effort is interpreted as rpm. 1 = 1 rpm.
Control word and Status word of the CiA 402 profile
Control word of CiA 402
Bit Description
0
Switch on
1
Enable voltage
2
Quick stop
3
Enable operation
4...6
Operation-mode-specific
7
Fault reset
8
Halt
9...10
Reserved
11...15
Drive-specific bit