Binary input object
Present
value ac-
cess type
Default
active/
Inactive
text
Description
Default object name
Object
ID
R
ON / OFF
Status of Relay Output 1
RO1-Monitor
BI0
R
ON / OFF
Status of Relay Output 2
RO2-Monitor
BI1
R
ON / OFF
Status of Relay Output 3
RO3-Monitor
BI2
R
ON / OFF
Status of Relay Output 4
RO4-Monitor
BI3
R
ON / OFF
Status of Relay Output 5
RO5-Monitor
BI4
R
ON / OFF
Status of Digital Output 1
DO1-Monitor
BI5
R
ON / OFF
Status of Digital Input 1
DI1-Monitor
BI6
R
ON / OFF
Status of Digital Input 2
DI2-Monitor
BI7
R
ON / OFF
Status of Digital Input 3
DI3-Monitor
BI8
R
ON / OFF
Status of Digital Input 4
DI4-Monitor
BI9
R
ON / OFF
Status of Digital Input 5
DI5-Monitor
BI10
R
ON / OFF
Status of Digital Input 6
DI6-Monitor
BI11
■
Binary output object
Present
value ac-
cess type
Default
active/
Inactive
text
Description
Default object name
Object
ID
C
ON / OFF
Output state of Relay 1
RO1-Command
BO0
C
ON / OFF
Output state of Relay 2
RO2-Command
BO1
C
ON / OFF
Output state of Relay 3
RO3-Command
BO2
C
ON / OFF
Output state of Relay 4
RO4-Command
BO3
C
ON / OFF
Output state of Relay 5
RO5-Command
BO4
C
ON / OFF
Output state of Digital Output 1
DO1-Command
BO5
44 Communication protocol
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...