Start-up
Contents of this chapter
This chapter contains:
•
information on configuring the drive for operation with the adapter module
•
drive-specific instructions on starting up the drive with the adapter module
•
information on configuring the client for communication with the adapter module.
Configuring the BACnet/IP connection
After the adapter module has been mechanically and electrically installed according
to the instructions in chapters
Mechanical installation (page 19)
and
, you must prepare the drive for communication with the module.
The detailed procedure for activating the module for BACnet/IP communication with
the drive depends on the drive type. Normally, you must adjust a parameter to activate
the communication. See
Starting up BACnet/IP communication for ACH480 and
Once communication between the drive and the adapter module has been established,
several configuration parameters are copied to the adapter module. These parameters
are shown in the tables below and must be checked first and adjusted where necessary.
You can adjust the parameters via a drive control panel or a PC tool.
Note: The new parameter settings take effect only when you power up the module
the next time or when you activate the fieldbus adapter refresh parameter.
■
FBIP-21 configuration parameters – group A (group 1)
Group A (group 1) corresponds to parameter group 51 in the drive.
6
Start-up 23
12
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...