Revision:
Language: Page:
A EN
4/7
1KHW001496-EN
2.4
Firmware download parameters
The
Firmware download
dialog box contains a field with download parameters. You can choose
either an automatic firmware download or a user controlled firmware download by deactivating the
check box.
2.4.1
Automatic firmware download
This is the recommended method to download the firmware. The HMI600 executes all necessary
actions for a proper operation. The checkbox
Automatic firmware download
has to be checked.
The download process compares the firmware version on the modules with the firmware version of
the selected download files. The download to a module is not executed if the versions are equal.
So only the modules are modified, which have not the same version as the selected download files.
2.4.2
User controlled firmware download
)
Note:
Only for authorized and properly trained persons.
The user controlled firmware download gives you the opportunity to modify one selected module in
a system. Deactivating the checkbox for automatic firmware download enables the button
Reset
system
. Please follow the instruction in the “
Download status & progress instruction
” window.
3 Firmware
download
3.1
Update of non-configured equipment
1. On
the
File
menu click
Open
. This opens the
Open
dialog box. Select the configuration file
and click
Open
.
2. From
the
Equipment
menu click
Connect
. This opens the
Connect
dialog box.
3. Click
Read & Write access
.
4. Click
OK
.
5. On
the
Equipment
menu, click
Commissioning and maintenance
and then click
Firmware
download…
6.
In the following message box click
Yes
if you are aware of a malfunction of the PLC link. This
opens the
Firmware download
dialog box. Otherwise click No.
7. The
checkbox
Automatic firmware download
has to be checked.
8. Click
Start firmware
download
to start the operation.
9.
The following message box informs you which download files are used. Be sure that all files
are from the same release directory.
Click
Yes
to accept these files. This starts the firmware download. The HMI600 automatically
performs the update and resets the system after the update is completed.
Click
No
to select other files. This opens a
file open
dialog box for each kind of download file.
Click
Cancel
to stop firmware download.
10.
Wait
until the
Close
button changes to the active state.
11. Click
Close
to leave the
firmware download
dialog box.
12. From the
Equipment
menu, click
Download configuration
. The license is checked and an
error message appears if it is not sufficient. Compatibility checks are performed to verify that
the firmware versions on the different modules in the equipment belong to the same release
as the HMI600. If not, an error message pops up. Depending on the message, an earlier
version of HMI600 must be used and/or the firmware of some modules must be upgraded.
13. If the
Download configuration
operation is possible, a message box appears, which informs
you that the link will be cut off for a few seconds.
Click
Yes
.
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......