Revision:
Language: Page:
A EN
11/28
1KHW001495-EN
)
Note:
The measured transmission time (T
nominal
) does not include the channel delay.
)
Note:
The nominal transmission time as given in the instruction manual shall serve
as a guideline for the mean value of several commands.
Get the link to normal operation as described in chapter C.1.
C.10.3 Reset
counters
After NSD600 testing is done, reset the counters by using HMI600.
1. Open the dialog
Equipment
/
Commissioning and maintenance
/
Eventrecorder
/
Reset counter
.
2. In
the
Reset Counter
box, click the check box
Reset all counters
.
3. Click
OK
.
C.11
Testing of O4LE, if present
The AF interface O4LE is tested by applying a test signal at the input ports and measure this signal
at the output ports. To get the input signals at the local output ports a local loop is necessary. The
local loop is established according to chapter C.1.
Make a printout of the actual configuration of the equipment using HMI600 and test all ports, which
are not in the off state.
C.11.1 Service
phone
The following tests must only be done, if the ‘Service phone’ is enabled.
Get the equipment in local loop operation according to chapter C.1. The service phone cannot be
tested completely in the local loop mode.
1. Pick up the phone and speak. You should hear yourself clearly. If a feedback tone
occurs, you should increase the difference between input level and output level of the
service phone in the configuration.
C.11.2
Hot line direct phone
The following tests must only be done, if the operation mode ‘Hot line direct phone’ is configured.
Get the equipment in local loop operation according to chapter C.1. This operation mode cannot be
tested completely in the local loop mode.
1. Measure the voltage at open loop condition:
Disconnect phone and take the measurement.
2. Check audibility of phone:
If the chosen phone is available, test the audibility:
Pick up the phone and speak. You should hear yourself clearly. If a feedback tone
occurs, you should increase the difference between input level and output level of the
‘subscriber, direct phone’ in the configuration.
C.11.3 ‘Remote
subscriber’
The following tests must only be done, if the operation mode ‘Remote subscriber’ is configured.
Get the equipment in local loop operation according to chapter C.1. This operation mode cannot be
tested completely in the local loop mode.
1. Measure the voltage at open loop condition:
Disconnect phone and take the measurement.
2. Check audibility of phone:
If the chosen phone is available, test the audibility:
Pick up the phone and speak. You should hear yourself clearly. If a feedback tone
occurs, you should increase the difference between input level and output level of the
‘subscriber, direct phone’ in the configuration.
Summary of Contents for ETL600
Page 4: ......
Page 32: ......
Page 126: ......
Page 176: ......
Page 206: ......
Page 216: ......
Page 226: ......
Page 264: ......
Page 268: ......
Page 276: ......
Page 284: ......
Page 308: ......
Page 324: ......
Page 346: ......
Page 348: ......
Page 366: ......
Page 372: ......
Page 374: ......
Page 380: ......