166 Commissioning instructions
Manual Energy Storage Inverter ESI-S
This operation has to be repeated for the remaining two phases for a complete check.
The current probes have to be changed accordingly.
8.6.2.4 Checking the correct connection of the CTs with a Fluke 41B or similar
equipment
The Fluke 41B is a power analyzer that allows measurements of one voltage and one
current wave. Unfortunately, the device does not allow simultaneous display of both
waveforms on the screen. However, it is possible to synchronize the triggering on either
the voltage or on the current. All phase shift measurements are then referenced to the
chosen origin. To read directly the phase shift between the fundamental components,
just select the spectrum window of the signal which is not chosen as the origin.
The instrument must be configured for single-phase measurements.
The probes must be connected as shown in
8.7 Step 6: Before starting the inverter
Before switching the system ON, ensure that:
−
The inverter is communicating well with the different components of the system
such as the Master Controller System. Verify that all battery information is
received by the inverter.
−
The battery voltage reported on the ESI-Manager (information coming from the
master controller) is matching the real battery voltage
−
The protection of the battery is closed
−
The battery is ready to start
Before switching the inverter ON, ensure that all features have been deselected.
−
For deselecting the active power target, set the target back to
zero.[/Welcome/Settings/BESS operation]
−
For deselecting all harmonics of the main inverter settings at once go to
[/Welcome/Settings/Customer set./Main settings/Deselect all]
−
For deselecting all harmonics of the auxiliary inverter settings at once go to
[/Welcome/Settings/Customer set./Auxiliary settings/Deselect all]
−
For deselecting the reactive power compensation option of the main inverter
settings disable the option ‘PFC type’ in
[/Welcome/Settings/Customer set./Main settings/Main PFC/Bal.]
−
For deselecting the load balancing option of the main inverter settings disable
the option ‘Balance load’ in
[/Welcome/Settings/Customer set./Main settings/Main PFC/Bal.]
−
For deselecting the reactive power compensation option of the auxiliary inverter
settings disable the option ‘PFC type’ in
[/Welcome/Settings/Customer set./Auxiliary settings/Aux. PFC/Bal.]