Endura AZ series integral and remote transmitter
Combustion oxygen monitor
5 Programming
IM/AZ20E–EN Rev. F
35
…Easy Setup
Temperature Units
Selects the units to be used for all temperature values in the
transmitter.
°C
°C
°F
Factory Cal. Offset
Used to enter the calibration offset value supplied with the
new probe / cell.
When changing the
Probe Type
to / from
AZ10
, the
following defaults are used:.
AZ10 = –10 mV
non-AZ10 = 0 mV
Note
. Refer to the label supplied with cell.
Factory Cal. Factor
Used to enter the calibration factor value supplied with the
new probe / cell.
Note
. Refer to the label supplied with cell.
1.00
New Probe/Cell Fitted
Used to confirm and setup a new probe or cell.
Select
OK
to confirm a new probe or cell has been fitted;
this resets the diagnostic measurements and states.
A new entry is created in the
Performance Log
to record
that a new cell or probe has been fitted and that factory
values have been entered.
N / A
Parameter
Comment / [Range]
Default
Table 5.6 Easy Setup Menu (Continued)