Technical Data
7.1
Electronics
1)
The 35 A fuse and the thermal safety cutout are included in the scope of delivery. They ensure safe
operation for the special swiching conditions of power electronics EBS862. Note that the cable cross-
sectional area between the fuse and the electronics must be at least 2.5 mm
2
.
7.2
Mounting Rack
Weigth of empty rack:
approx. 40 kg
Weight of rack with units:
approx. 210 kg
Electronics
EAS822
EBS852
EBS862
Protection class
IP 20
Humidity
≤
75% annual average, no condensation permitted
Intake air temperature at
mounting rack
0 ... . 45° C
Mounting orientation
Vertical, connections from bottom or right
Varnish
2-component epoxy resin (RAL 9005, black)
Vibration
2 … 9 Hz:
max. excursion: 3 mm
9 … 200 Hz:
acceleration: 1 g
Weight
approx. 9 kg
approx. 11 kg
approx. 40 kg
Electrical connection
Power supply via screw terminals,
all other connections via plug-in connection
Cable connection
(solid or stranded)
Signal:
min 0.5
2
; max. 1.5
2
Motor:
min 0.5
2
; max. 2.5
2
Mains:
min 0.5
2
; max. 4.0
2
Signal: min
0.5
2
; max. 1.5
2
Motor: min
0.5
2
; max. 4.0
2
Mains: min
0.5
2
; max. 4.0
2
External series fuse
1)
16 A (slow-blow)
35 A fuse
16 A thermal safety cutout
Supply voltage
230 V AC (190 V ... 260 V) or
115 V AC (94 V ... 130 V);
50/60 Hz ± 5%; 1 Ph
230 V AC (190 V ... 260 V)
50/60 Hz ± 5%; single-phase
Analog input, set value
0 / 4 … 20 mA
Analog output, actual
value
0 / 4 … 20 mA; electrically isolated
Output; U
V
24 VDC; 15 mA for supply of digital inputs
Digital inputs, DI 1 … 3
Electrically isolated via opto-couplers
Logical 0: -3V … + 5 V or open; Logical 1: +12 V …+ 35 V
Digital outputs, DO 1 …
Potential-free relay contact, max. 60 V DC / 25 V AC; 150 mA
Analog input, transmitter
Supply and signal input for 2-wire transmitter
Digital communication
RS 232 for commissioning and service; optionally HART
®/
FSK
Default settings
Function:
positioner
Set value function:
linear, (set value = positioning value)
Set value input:
4 … 20 mA
Actual value output:
4 … 20 mA
Behavior in 0/100% end position: shut-off with rated force / rated torque
Digital inputs:
DI 1 M/A selection; DI2 / DI3 manual
interact. +/-
Digital outputs:
DO 1 ready;
DO 2/3 end position signalling 0/100%
Table 1: