9.6
Cable guidance at the plug
Pass and connect both the signal and the power cable separately within the plug housing in order to
avoid electro magnetic interferences. A metal plate separates both cable areas from eachother. Con-
nect the screen acc. to fig. 12.
Fig. 12:
Cable guidance within the plug
9.7
Fuses
9.7.1
EAS822
9.7.2
EBS852
Type
Location
U
V
= 115 V
U
V
= 230 V
Series fuse
external
16 A; slow-blow
Mains fuse
F1, in terminal box
6.3 A; slow-blow
3.15 A; slow-blow
Relay fuse for DO1, DO2, DO3 F2 ... F4; in terminal box
3 x 0.2 A; medium time-lag
Table 4:
Type
Location
U
V
= 115 V
U
V
= 230 V
Series fuse
external
16 A; slow-blow
Mains fuse
F1, in terminal box
12.5 A; slow-blow
10 A; slow-blow
Relay fuse for DO1, DO2, DO3
F2 ... F4; in terminal box
3 x 0,2 A; medium time-lag
Brake fuse
on board (power sec-
tion)
0,315 A; medium time-lag
Intermediate circuit fuse
Power board
10 A; super-quick
Table 5:
Leistungskabel
Trenn-
steg
Signal-
kabel
Abschirmung
Abschirmung