ACH550-UH User’s Manual
87
2108
START INHIBIT
0, 1
1
0
9
Sets the Start inhibit function on or off. The Start inhibit function ignores a pending start command in any of the
following situations (a new start command is required):
• A fault is reset.
• Run Enable (parameter 1601) activates while start command is active.
• Mode changes from local to remote.
• Mode changes from remote to local.
• Control switches from
EXT
1 to
EXT
2.
• Control switches from
EXT
2 to
EXT
1.
0 =
OFF
– Disables the Start inhibit function.
1 =
ON
– Enables the Start inhibit function.
2109
EM STOP SEL
-6…6
1
0
Defines control of the Emergency stop command. When activated:
• Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208 EM DEC TIME).
• Requires an external stop command and removal of the emergency stop command before drive can restart.
0 =
NOT
SEL
– Disables the Emergency stop function through digital inputs.
1 =
DI
1 – Defines digital input
DI
1 as the control for Emergency stop command.
• Activating the digital input issues an Emergency stop command.
• De-activating the digital input removes the Emergency stop command.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for Emergency stop command.
• See
DI
1 above.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for Emergency stop command.
• De-activating the digital input issues an Emergency stop command.
• Activating the digital input removes the Emergency stop command.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for Emergency stop command.
• See
DI
1(
INV
) above.
2110
TORQ BOOST CURR
0…300%
1
100%
Sets the maximum supplied current during torque boost.
• See parameter 2101
START
FUNCTION
.
Group 21: Start/Stop
Code Description Range
Resolution
Default