ACH550-UH User’s Manual
51
Parameter Descriptions
Parameter data is specific to ACH550 firmware version 1.51.
Group 99: Start-up Data
This group defines special Start-up data required to:
•
Set up the drive.
•
Enter motor information
Note!
Parameters checked under the heading “S” can be modified only when the
drive is stopped.
Group 99: Start-up Data
Code Description Range
Resolution
Default
S
9901
LANGUAGE 0…10
1
0
Selects the display language.
9902
APPLIC MACRO
1…14
1
1
9
Selects an application macro. Application macros automatically edit parameters to configure the ACH550 for a
particular application. See "Application Macros" for application macro descriptions.
1 =
HVAC
DEFAULT
2 =
SUPPLY
FAN
3 =
RETURN
FAN
4 =
COOLING
TOWER
FAN
5 =
CONDENSER
6 =
BOOSTER
PUMP
7 =
PUMP
ALTERNATION
8 =
INTERNAL
TIMER
9 =
INTERNAL
TIMER
WITH
CONSTANT
SPEEDS
10 =
FLOATING
POINT
11 =
DUAL
SETPOINT
PID
12 =
DUAL
SETPOINT
PID
WITH
CONSTANT
SPEEDS
13 =
E
-
BYPASS
14 =
HAND
CONTROL
9904
MOTOR CTRL MOD
1, 3
1
3
9
Selects the motor control mode.
1 =
VECTOR
: s
PEED
– sensorless vector control mode.
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
MAXIMUM
SPEED
, or 2001
MINIMUM
SPEED
if the absolute value of the minimum speed is greater than the maximum
speed).
3 =
SCALAR
:
FREQ
– scalar control mode.
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM
FREQUENCY
, or 2007
MINIMUM
FREQUENCY
if the absolute value of the minimum speed is greater
than the maximum speed).
0 =
ENGLISH
1 =
ENGLISH
(
AM
)
2 =
DEUTSCH
3 =
ITALIANO
4 =
ESPAÑOL
5 =
PORTUGUES
6 =
NEDERLANDS
7 =
FRANCAIS
8 =
DANSK
9 =
SUOMI
10 =
SVENSKA