2.6.4 Setting of air pressure switch (only applicable to type S)
General
The digital pressure switch monitors the shop floor air pressure.
Settings
The procedure below details how to set the digital pressure switch. The example
shows how to set according to the pre-set values. The sensor will set
g1_air_ok
in the robot controller when pressure reaches 0.5 MPa and reset
g1_air_ok
if
pressure goes lower than 0.45 MPa.
Note
Action
Mode
Make sure that the pressure switch is connected
to 12-24 VDC power.
Preparation
1
0
In measurement mode, press SET button for two
seconds or more.
Initialize
2
PA
Press UP or DOWN button until the display
matches the figure on the right, then press the
SET button.
Selection of Unit
3
PA indicates MPa.
1no
Press UP or DOWN button until display matches
the figure on the right, then press the SET but-
ton.
OUT1 Output
type Setting
4
("
1no
" = Output 1
normally open)
2n*
Ignore and press the SET button.
OUT2 Output
type Setting
5
24
Press UP or DOWN button until display matches
the value on the right, then press the SET button.
Response Time
Setting
6
ñAn
Press UP or DOWN button until display matches
the value on the right, then press the SET button.
Auto/Manual
Setting
7
(
ñAn
indicates
manual setting)
In measurement mode, press the SET button.
Value Setting
8
P_1
When the display blinks, press UP or DOWN
button without pressing the SET button.
Set Point Value
for OUT1(1)
9
0.500
Press UP or DOWN button until the display
matches the value on the right, then press the
SET button.
Pressure OK
goes high
P_2
When the display blinks, press UP or DOWN
button without pressing the SET button.
Set Point Value
for OUT1(2)
10
0.450
Press UP or DOWN button until the display
matches the value on the right, then press the
SET button.
Pressure OK
goes low
P/n3
Ignore and press the SET button.
Set Point Value
for OUT2(1)
11
P/n4
Ignore and press the SET button.
Set Point Value
for OUT2(2)
12
0
The pressure switch changes to measurement
mode. All settings are completed.
13
0
Press UP and DOWN buttons simultaneously
for about 2 seconds, under atmospheric pres-
sure.
Zero Clear Func-
tion
14
Continues on next page
190
Product manual - DressPack/SpotPack IRB 6640
3HAC028638-001 Revision: K
© Copyright 2007-2018 ABB. All rights reserved.
2 Installation
2.6.4 Setting of air pressure switch (only applicable to type S)
Summary of Contents for DressPack IRB 6640
Page 1: ...ROBOTICS Product manual DressPack SpotPack IRB 6640 ...
Page 8: ...This page is intentionally left blank ...
Page 18: ...This page is intentionally left blank ...
Page 44: ...This page is intentionally left blank ...
Page 194: ...This page is intentionally left blank ...
Page 220: ...This page is intentionally left blank ...
Page 324: ...This page is intentionally left blank ...
Page 338: ...This page is intentionally left blank ...
Page 364: ...This page is intentionally left blank ...
Page 366: ...This page is intentionally left blank ...
Page 369: ......