Modifications reserved
Page 54/79
7.2.1
Remote shutdown
The REMOTE SHUT DOWN must use a normally closed contact, which opens to operate the remote
shut down sequence.
The remote shutdown on terminal port X1/7.. X1/8 is located at the bottom of the DPA UPSCALE
TM
frame on communication card with terminal blocks X. See chapter 6.4.3 for details.
In order to allow removal, maintenance or testing of any remote shut down facility without disturbing
the normal operation of the UPS, it is recommended that a terminal block, with linking facilities, be
installed between the UPS and the stop button.
1.
Use a screened cable with 1 pair (section of wires 0.5 mm
2
) and maximum length of 100 m.
2.
Connect the cable as shown in Fig. 7.2.1-1
REMOTE SHUT DOWN SWITCH
(N.C. = Normally Closed)
UPS
Remote shut down
(X1)
Terminal Block
Fig 7.2.1-1: Remote shutdown
7.2.2
Generator ON facilities
The Generator ON facility must use a normally open contact that closes to indicate that a generator is
running and supplying input power to the UPS. It is located at the bottom of the DPA UPSCALE
TM
frame on the communication card with terminal blocks X1 …X2. See chapter 6.4.3 for details.
When used, this facility disables the UPS static bypass and prevents the UPS from transferring the
load onto the generator power supply.
Generator alarm panel
UPS
Generator port
X1
Fig 7.2.2-1: Generator ON facilities
X
1
X
2
X1/7
X1/8
X1/1
X1/2
X
1
X
2
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...