Modifications reserved
Page 34/79
5.6
External batteries
WARNING!
KEEP AWAY FROM BATTERY POLES AS THESE CARRY DANGEROUS DC
VOLTAGES THAT CAN CAUSE FATAL ACCIDENTS.
NOTE:
MANIPULATION OF THE BATTERY SYSTEM SHOULD ONLY BE
PERFORMED BY TRAINED SERVICE AND MAINTENANCE PERSONNEL
FROM THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS.
INAPPROPRIATE MANIPULATIONS OF THE BATTERIES CAN CAUSE
SPARKS. WHILE WORKING ON BATTERY SYSTEMS IT IS MANDATORY TO
WEAR PROTECTIVE GLASSES
5.6.1
External battery configuration
In the DPA UPScale
TM
ST 80, ST 120 and ST 200 UPS cabinets there is no space provided for
batteries.
There are two external matching battery cabinets available:
•
CBAT UPScale -120 for Separate or Common battery configurations of 24Ah or 28Ah blocks
(max. 120 Blocks)
•
CBAT UPScale-200 for Separate or Common battery configurations for 24Ah or 28Ah blocks
(max. 200 Blocks)
S-type = For Separate. Battery
C-type = For Common. Battery
CBAT-UPScale-120
S-type or C-type
CBAT-UPScale-200
S-type or C-type
Battery frames
Configuration accommodates:
Max.
120 Batt. block x
24Ah/28Ah
on 8 shelf
3x5=15 blocks/shelf
200 Batt. blocks x
24Ah/28Ah
on 7 shelf
6x5=30 blocks/shelf
Battery fuses / Max. Batt. Strings :
Terminals :
S-type
9 / 3
(Terminal 9 x 16/25mm2)
15 / 5
(Terminal 15 x 16/25mm2)
Battery fuses / Max. Batt. Strings
Terminals :
C-type
9 / 3
+ Com. Connection
Bar
3 x (2xM8) +PE 2xM8
15 / 5
+ Com. Connection
Bar
3 x (2xM10) +PE
2xM10
Fuse Type (Very Fast acting)
A
3x100 A
5x100A
Dimensions (WxHxD)
mm
730x1975x800
1200x1975x800
Weight with trays and w/o batteries kg
290
410
For detailed information on, and layout of, the battery cabinets please refer to the “external battery
cabinets” chapter in the technical data sheet.
Summary of Contents for DPA UPScale ST40
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...