9.4
Customer interfaces: input and output dry ports
Block Terminal Contact
Signal On Display
Function
X 2
X 2 / 1 NO
MAINS_OK
Mains present
X 2 / 2 NC
ALARM
Mains failure
X 2 / 3 C
Common
X 2 / 4 NO
LOAD_ON_INV
Load on inverter
X 2 / 5 NC
Message
(Load on mains bypass)
X 2 / 6 C
Common
X 2 / 7 NO
BATT_LOW
Battery low
X 2 / 8 NC
ALARM
Battery OK
X 2 / 9 C
Common
X 2 / 10 NO
LOAD_ON_MAINS Load on bypass (Mains)
X 2 / 11 NC
Message
(Load on inverter)
X 2 / 12 C
Common
X 2 / 13 NO
COMMON_ALARM Common ALARM (System)
X 2 / 14 NC
ALARM
NO alarm condition
X 2 / 15 C
Common
X1
X1 / 1
IN
+ 12
VDC
Generator operation
X1 / 2
GND
GND
(NC = Generator ON)
X1 / 3
IN
+ 12
VDC
Customer IN 1
X1 / 4
GND
GND
(Function on request, to be defined)
X1 / 5
IN
+ 3.3
VDC
Temperature battery
X1 / 6
GND
GND
(If connected, the battery charger
current if depending on the battery
temp.)
X1 / 7
IN
+ 12
VDC
Remote shutdown
X1 / 8
GND
GND
(Do not remove the factory mounted
bridge until external remote
shutdown is connected)
X1 / 9
IN
+ 12
VDC
12 VDC source
X1 / 10 GND
GND
(max. 200 mA load)
All voltage-free contacts are rated 60 VAC max. and 500 mA max.
All the interfaces are connected to Phoenix spring terminals with wires (0.5 mm
2
)
Summary of Contents for DPA UPScale ST120
Page 1: ... Copyright 2017 ABB All rights reserved User Manual DPA UPScaleTM ST S2 10 200 kW ...
Page 76: ...Modifications reserved Page 76 79 10 Attachments 10 1 Technical data sheet ...
Page 78: ......
Page 79: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...
Page 104: ......
Page 105: ... Copyright 2017 ABB All rights reserved Technical data sheet DPA UPScaleTM ST S2 10 200 kW ...