Section-2
04-3006_S2_OPM_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc
Page 3/14 ABB
Modifications reserved
2.1.3 BLOCK DIAGRAM
DPA UPSCALE™
2.1.3.1
Single Feed input (Standard Version)
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
2.1.3.2
SINGLE FEED INPUT / Cable Sections
Enclosure
type
Load
in KW
Input 3x400V/230V
Output 3x400V/230V
@ cosphi 1.0
Battery
Fuse A
(Agl/CB)
Cable A
(mm
2
)
(IEC 60950-1)
Max. Input Current
with battery
charging (A)
Cable D
(mm
2
)
(IEC 60950-1)
I nom
(A)
Fuse E
+ / N / -
(Agl/CB)
Cable E (mm
2
)
Only for external Batteries
+ / N / -
Com.
Battery
Sep. Battery
Upscale RI 10
20
3x40A
5x6
34
5x6
29 A
3x63A
n.a.
3x10
Upscale RI 11
20
3x40A
5x6
34
5x6
29 A
3x63A
n.a.
n.a.
Upscale RI 12
20
3x40A
5x6
34
5x6
29 A
3x63A
n.a.
n.a.
Upscale RI 20
40
3x80A
5x16
68
5x16
58 A
3x100A *1
3x25 *1
2x(3x10)
Upscale RI 22
40
3x80A
5x16
68
5x16
58 A
3x100A *1
n.a.
n.a.
Upscale RI 24
40
3x80A
5x16
68
5x16
58 A
3x100A *1
n.a.
n.a.
Upscale RI 40
80
3x160A
5x50
136 A
5x50
116 A
3x224A*1
3x95 *1
4x(3x10)
*1 only valid for common battery use
n.a. = not allowed
Summary of Contents for DPA Upscale RI Series
Page 27: ......
Page 28: ......
Page 29: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 52: ......
Page 53: ......