29
Electrical installation
3ADW000379R0501 DCS550 Manual e e
⑥
Cooling fans
Fan assignment for DCS550:
Converter type
Size
Configuration
Fan type
DCS550-S01-0020, …,
DCS550-S02-0025
F1
-
No fan, convection cooled
DCS550-S01-0045, …,
DCS550-S02-0100
1
1 x 3110 KL-05W (internal 24 V
DC
)
DCS550-S01-0135, …,
DCS550-S02-0300
F2
2
2 x 4715 MS-12T (115 V
AC
/ 230 V
AC
)
DCS550-S01-0315, …,
DCS550-S02-0450
F3
DCS550-S01-0470, …,
DCS550-S02-0520
3
2 x 4715 MS-12T (115 V
AC
/ 230 V
AC
)
2 x 3115 FS-12T (115 V
AC
/ 230 V
AC
)
DCS550-S01-0610, …,
DCS550-S02-0820
F4
4
1 x W2E200 (230 V
AC
)
DCS550-S01-0900, …,
DCS550-S02-1000
1 x W2E250 (230 V
AC
)
Fan data for DCS550:
Fan
3110 KL-05W
4715 MS-12T
3115 FS-12T
W2E200
W2E250
Rated voltage [V
AC
]
24 V
DC
①
115; 1~
115; 1~
230; 1~
230; 1~
Tolerance [%]
+15 / -50
± 10
± 10
+6 / -10
+6 / -10
Frequency [Hz]
-
50
60
50
60
50
60
50
60
Power consumption [W]
2.88
16
13
9.5
8.0
64
80
135
185
Current consumption [A]
0.12
0.2
0.17
0.075
0.060
0.29
0.35
0.59
0.82
Blocking current [A]
-
< 0.3
< 0.26
< 0.085 < 0.075
< 0.7
< 0.8
< 0.9
< 0.9
Air flow [m
3
/h] freely blowing
66
156
180
47.5
55
925
1030
1860
1975
Max. ambient temp. [°C]
< 70
< 60
< 70
< 70
< 60
Useful lifetime of grease
approximately
70,000 h / 25°
approximately
40,000 h / 60°
approximately
50,000 h / 20°
approximately 40,000 h / 60°
Protection
DC
Impedance
②
Impedance
Internal temperature detector
①
Internally
connected
②
Increased losses due to increased current with a blocked rotor will not result in a winding temperature, higher than
permissible for the insulation class being involved.
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...