229
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
44.03 M1TiFex (i-part field current controller)
Integral time of the field current controller. M1TiFex (44.03) defines the time within the integral part of the
controller achieves the same value as the proportional part.
Example:
The controller generates 15 % of motor nominal field current [M1NomFldCur (99.11)] with M1KpFex (44.02) =
3, if the field current error is 5 % of M1NomFldCur (99.11). On that condition and with M1TiFex (44.03) = 200
ms follows:
−
the controller generates 30 % of motor nominal field current, if the current error is constant, after 200 ms
are elapsed (15 % from proportional part and 15 % from integral part).
Setting M1TiFex (44.03) to 0 ms disables the integral part of the field current controller and resets its
integrator.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
64000
200
ms
44.04 M1FldHeatRef (field heating reference)
Field current reference - in percent of M1NomFieldCur (99.11) - for field heating. Field heating is released
according to FldHeatSel (21.18).
Int. Scaling: 1 == 1 %
Type: I
Volatile:
N
0
100
100
%
44.05 - 44.06 Unused
44.07 EMF CtrlPosLim (positive limit EMF controller)
Positive limit for EMF controller in percent of nominal flux.
Int. Scaling: 1 == 1 %
Type: I
Volatile:
N
0
100
10
%
44.08 EMF CtrlNegLim (negative limit EMF controller)
Negative limit for EMF controller in percent of nominal flux.
Int. Scaling: 1 == 1 %
Type: I
Volatile:
N
-100
0
-100
%
44.09 KpEMF (p-part EMF controller)
Proportional gain of the EMF controller.
Example:
The controller generates 15 % of motor nominal EMF with KpEMF (44.09) = 3, if the EMF error is 5% of
M1NomVolt (99.02).
Int. Scaling: 100 == 1
Type: I
Volatile:
N
0
325
0
.5
-
44.10 TiEMF (i-part EMF controller)
Integral time of the EMF controller. TiEMF (44.10) defines the time within the integral part of the controller
achieves the same value as the proportional part.
Example:
The controller generates 15 % of motor nominal EMF with KpEMF (44.09) = 3, if the EMF error is 5% of
M1NomVolt (99.02). On that condition and with TiEMF (44.10) = 20 ms follows:
−
the controller generates 30 % of motor nominal EMF, if the EMF error is constant, after 20 ms are elapsed
(15 % from proportional part and 15 % from integral part).
Setting TiEMF (44.10) to 0 ms disables the integral part of the EMF controller and resets its integrator.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
64000
50
ms
44.11 Unused
44.12 FldCurFlux40 (field current at 40% flux)
Field current at 40 % flux in percent of M1NomFldCur (99.11).
Int. Scaling: 1 == 1 %
Type: I
Volatile:
N
0
100
40
%
44.13 FldCurFlux70 (field current at 70% flux)
Field current at 70 % flux in percent of M1NomFldCur (99.11).
Int. Scaling: 1 == 1 %
Type: I
Volatile:
N
0
100
70
%
44.14 FldCurFlux90 (field current at 90% flux)
Field current at 90 % flux in percent of M1NomFldCur (99.11).
Int. Scaling: 1 == 1 %
Type: I
Volatile:
N
0
100
90
%
Group 45: Field converter settings
45.01 Unused
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...