Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
22.11 Ramp2Select (ramp 2 selector)
Select active ramp parameters:
0 = Acc/Dec1
parameter set 1 [AccTime1 (22.01) and DecTime1 (22.02)] is active, default
1 = Acc/Dec2
parameter set 2 [AccTime2 (22.09) and DecTime2 (22.10)] is active
2 = SpeedLevel
If |SpeedRef3 (2.02)|
≤
|SpeedLev (50.10)|, then parameter set1 is active.
If |SpeedRef3 (2.02)| > |SpeedLev (50.10)|, then parameter set 2 is active.
3 = DI1
0 = parameter set 1 is active, 1 = parameter set 2 is active
4 = DI2
0 = parameter set 1 is active, 1 = parameter set 2 is active
5 = DI3
0 = parameter set 1 is active, 1 = parameter set 2 is active
6 = DI4
0 = parameter set 1 is active, 1 = parameter set 2 is active
7 = DI5
0 = parameter set 1 is active, 1 = parameter set 2 is active
8 = DI6
0 = parameter set 1 is active, 1 = parameter set 2 is active
9 = DI7
0 = parameter set 1 is active, 1 = parameter set 2 is active
10 = DI8
0 = parameter set 1 is active, 1 = parameter set 2 is active
11 = DI9
0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital
extension board
12 = DI10
0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital
extension board
13 = DI11
0 = parameter set 1 is active, 1 = parameter set 2 is active, only available with digital
extension board
14 = MCW Bit11
0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 11
15 = MCW Bit12
0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 12
16 = MCW Bit13
0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 13
17 = MCW Bit14
0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 14
18 = MCW Bit15
0 = parameter set 1 is active, 1 = parameter set 2 is active, MainCtrlWord (7.01) bit 15
Int. Scaling: 1 == 1
Type: C
Volatile:
N
A
cc/
D
c
c1
M
C
W
B
it
15
A
cc/
D
c
c1
-
22.12 JogAccTime (acceleration time jogging)
The time within the drive will accelerate from zero speed to SpeedScaleAct (2.29) in case of jogging:
−
When using jog command Jog1 (10.17) or MainCtrlWord (7.01) bit 8 speed is set by FixedSpeed1 (23.02)
−
When using jog command Jog2 (10.18) ) or MainCtrlWord (7.01) bit 9 speed is set by FixedSpeed2
(23.03)
Int. Scaling: 100 == 1 s
Type: I
Volatile:
N
0
300
20
s
22.13 JogDecTime (deceleration time jogging)
The time within the drive will decelerate from SpeedScaleAct (2.29) to zero speed in case of jogging:
−
When using jog command Jog1 (10.17) or MainCtrlWord (7.01) bit 8 speed is set by FixedSpeed1 (23.02)
−
When using jog command Jog2 (10.18) ) or MainCtrlWord (7.01) bit 9 speed is set by FixedSpeed2
(23.03)
Int. Scaling: 100 == 1 s
Type: I
Volatile:
N
0
300
20
s
Group 23: Speed reference
23.01 SpeedRef (speed reference)
Main speed reference input for the speed control of the drive. Can be connected to SpeedRefUsed (2.17) via:
−
Ref1Mux (11.02) and Ref1Sel (11.03) or
−
Ref2Mux (11.12) and Ref2Sel (11.06)
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-10000
10000
0
rp
m
23.02 FixedSpeed1 (fixed speed 1)
FixedSpeed1 (23.02) is specifying a constant speed reference and overrides SpeedRef2 (2.01) at the speed
ramps input. It can be released by Jog1 (10.17) or MainCtrlWord (7.01) bit 8. The ramp times are set with
JogAccTime (22.12) and JogDecTime (22.13).
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Int. Scaling: (2.29)
Type: SI
Volatile:
N
-10000
10000
0
rp
m
Summary of Contents for DCS550 Series
Page 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Page 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Page 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...