ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
65
6.7.3
Practice via PLC
This section shows a demo about how to read system
status using a Programmable logic controller (PLC). We use
AC500 and Automation Builder as a development platform.
We choose the same Modbus ID, baud rate and frame
format as previous practice. These settings can be
configured in Modbus parameters in Automation Builder.
A build-in function block from AC500, “COM_MOD_MAST”,
is used for sending/receiving Modbus telegrams via COM
interface. Do the following steps to set up a program
with Ladder:
• CSU2_COM: COM_MOD_MAST;
• enable: BOOL;
• READ_VALUE: ARRAY [1..15] OF UINT;
• FCT_READ_HOLDING_REGISTERS:BYTE:=3;
• NUM_VARIALBE_READ: UINT := 1;
• REGISTER_ADDRESS:BYTE:=100;
• TIMEOUT_TIME: WORD := 1000;
• SLAVE_ID: BYTE := 5;
We set up the network as following:
Results are shown in READ_VALUE array.
Figure 36
PLC network
1SFC170020M0201
06
Summary of Contents for CSU-2LV
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 12: ......
Page 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Page 18: ......
Page 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Page 30: ......
Page 38: ......
Page 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Page 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Page 70: ......
Page 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Page 76: ......
Page 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...