42
ABB
ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
Select Baud rate according to the existing network.
On delivery the default value for Baud rate is 19200.
Select Frame format according to the existing network.
On delivery the default value for Frame format is 8 bits,
even, stop 1.
Figure 33
Settings menu
1SFC170020M020
1
Figure 34
Settings menu
1SFC170020M020
1
6.5
Configuration
Modbus configuration is done via the HMI.
Access the Modbus configuration page by first
selecting Settings on the Main page.
In the sub-menu for Modbus, configure Modbus ID,
Baud rate and Frame format.
Select Modbus ID according to the existing network.
On delivery the default value for Modbus ID is 248.
Figure 30
Settings menu
1SFC170020M020
1
Figure 31
Settings menu
1SFC170020M020
1
Figure 32
Settings menu
1SFC170020M020
1
06