7.9 System failure when changing PROFINET-based laser scanner to SafetyIO-based
laser scanner
Description
The robot configured with PROFINET-based laser scanner(s) needs to replace
with SafetyIO-based laser scanner. During system update using the
Installation
Manager
, system failure occurs after removing the profisafe package option(s)
and selecting required IO package option(s).
Consequence
The system cannot be successfully set up.
Possible causes
Option
3020-2 PROFINET Device
and option
3023-2 PROFIsafe Device
are removed
together with the profisafe package option(s), and the safety configurations become
invalid.
Recommended actions
1 On the home page of the FlexPendant, tap
Settings
.
2 Tap
Backup & Recovery
.
3 Tap
Reset user data
.
4 Select
Reset safety settings
.
5 Tap
Reset
.
6 Restart the controller.
If the problem persists, reinstall the system.
1070
Product manual - CRB 15000
3HAC077389-001 Revision: L
© Copyright 2021 - 2023 ABB. All rights reserved.
7 Troubleshooting
7.9 System failure when changing PROFINET-based laser scanner to SafetyIO-based laser scanner
Summary of Contents for CRB 15000
Page 1: ...ROBOTICS Product manual CRB 15000 ...
Page 8: ...This page is intentionally left blank ...
Page 16: ...This page is intentionally left blank ...
Page 38: ...This page is intentionally left blank ...
Page 54: ...This page is intentionally left blank ...
Page 182: ...This page is intentionally left blank ...
Page 200: ...This page is intentionally left blank ...
Page 1058: ...This page is intentionally left blank ...
Page 1076: ...This page is intentionally left blank ...
Page 1095: ......