7.8 Communication failure between scalable I/O device and controller
Description
The OmniCore controller and scalable I/O device DSQC1042 are configured with
all parameters correctly set. However, the communication between the OmniCore
controller and scalable I/O device still fails.
This issue may occur when the SafetyIO-based laser scanner(s) is connected.
Consequence
The safety configurations do not take effect.
Possible causes
During configuration of communication between the OmniCore controller and
scalable I/O device, the scalable I/O device information must be configured on the
OmniCore controller’s side first. Otherwise, the configured signals will not be saved
in the OmniCore controller.
Recommended actions
1 Open the RobotStudio.
2 In the
Controller
tab page, choose
Visual SafeMove
from
Safety
in the
Configuration
group.
3 Check the Safe I/O configurations.
The following signals can be observed.
xx2200000305
4 If the signals cannot be observed, choose
I/O Engineering Tool
from
Configuration
in the
Configuration
group.
5 Go back to the
Visual SafeMove
window and write the SafeMove
configurations to the controller again.
You will observe the signals and the communication is correctly set up.
Product manual - CRB 15000
1069
3HAC077389-001 Revision: L
© Copyright 2021 - 2023 ABB. All rights reserved.
7 Troubleshooting
7.8 Communication failure between scalable I/O device and controller
Summary of Contents for CRB 15000
Page 1: ...ROBOTICS Product manual CRB 15000 ...
Page 8: ...This page is intentionally left blank ...
Page 16: ...This page is intentionally left blank ...
Page 38: ...This page is intentionally left blank ...
Page 54: ...This page is intentionally left blank ...
Page 182: ...This page is intentionally left blank ...
Page 200: ...This page is intentionally left blank ...
Page 1058: ...This page is intentionally left blank ...
Page 1076: ...This page is intentionally left blank ...
Page 1095: ......