7.7 Communication failure between PLC and controller
Description
The OmniCore controller and PLC are configured with all parameters correctly set.
However, the communication between the OmniCore controller and PLC still fails.
This issue may occur when the PROFIsafe-based laser scanner(s) is connected.
Consequence
The safety configurations do not take effect.
Possible causes
During configuration of communication between the OmniCore controller and PLC,
the PROFIsafe device information must be configured on the OmniCore controller’s
side first. Otherwise, the configured signals will not be saved in the safety module
in the OmniCore controller.
Recommended actions
1 Open the RobotStudio.
2 In the
Controller
tab page, choose
Visual SafeMove
from
Safety
in the
Configuration
group.
3 Check the Safe I/O configurations.
For robots running RobotWare 7.5 or earlier, the following signals can be
observed.
xx2100000511
Continues on next page
Product manual - CRB 15000
1067
3HAC077389-001 Revision: L
© Copyright 2021 - 2023 ABB. All rights reserved.
7 Troubleshooting
7.7 Communication failure between PLC and controller
Summary of Contents for CRB 15000
Page 1: ...ROBOTICS Product manual CRB 15000 ...
Page 8: ...This page is intentionally left blank ...
Page 16: ...This page is intentionally left blank ...
Page 38: ...This page is intentionally left blank ...
Page 54: ...This page is intentionally left blank ...
Page 182: ...This page is intentionally left blank ...
Page 200: ...This page is intentionally left blank ...
Page 1058: ...This page is intentionally left blank ...
Page 1076: ...This page is intentionally left blank ...
Page 1095: ......