ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
7 Advanced Level
46
IM/CM/ED–EN Rev. X
7.4 Control
Enables the setpoints, control functions and outputs to be configured.
Loop 1 (2) Setpoints
The controller can have up to 4 independent local setpoint values, remote setpoint
functionality and the ability to limit the absolute values and rate of change of the control
setpoint.
Loop 2 Setpoint
settings apply to the slave controller if a
Cascade
application template
is selected – see Section 8, page 88 for template options.
Note
. This section is not applicable for
Auto/Manual Station
,
Single & Dual Indicator
,
Ratio
Station templates
– see Section 8, page 88 for template options.
Low Limit
High Limit
The setpoint limit parameters define the maximum and minimum values for the local and/or
remote setpoints. The setpoint limits do not apply when in
Manual
control mode with local
setpoint tracking enabled. If the setpoint is outside of limits when
Auto
control mode is
selected, the setpoint value can be adjusted only towards its limits.
Once within the limits they apply as normal.
No. of Local
S
P's
Selects the number of independent local (internal) setpoints required.
The local setpoints can be selected from the
Operator
level menu or via a digital signal.
Local
S
etpoint 1 (4)
If the value is adjusted in the
Operator
level, its value here is also updated.
Track Mode
The local (internal) setpoint can track another value according to the setpoint tracking
mode selected.
Off
No tracking.
Local
The local (internal) setpoint tracks the process variable when
Manual
control mode is
selected.
Remote
The local (internal) setpoint tracks the remote (external) setpoint when in
Remote Setpoint
mode. If the controller is put into
Manual
control mode the setpoint reverts from
Remote
to
Local
. This also applies to the local and remote ratio when a ratio controller template is
selected – see Section 8, page 88 for template details.
Note
. Available only if the template selected has remote setpoint or ratio functionality.
Local and Remote
Note
. Available only if the template selected has remote setpoint or ratio functionality.
Menu
Control
Exit
Select