Page 59/94
6.6.4
"MAINTENANCE BYPASS" - Mode
Before transferring the load to Maintenance Bypass (IA1) always make sure all the UPS-modules are
in the "Bypass-Mode” or “ECO-Mode”. The Maintenance Bypass mode is performed by closing (put
in position ON) the IA1 Maintenance Bypass switch on the front of the UPS.
POSITION OF IA1 EFFECT
ON
Bypass-Switch Closed (Load supplied directly from mains)
LCD-indication: “MANUAL BYP IS CLOSED” LED Indicators will indicate as
shown in table below.
OFF
Bypass-Switch Open – Normal operating condition (Load supplied by inverter)
LCD-indication “MANUAL BYP IS OPEN”
LED Indicators will indicate as shown in table below.
Bypass Switch
LED Indicator
ON
OFF
LINE 1
Green
Green
LINE 2
Green
Green
BYPASS
Green
OFF
INVERTER
RED
Green
BATTERY
Green
Green
NOTE
ON OPERATION MODE “MANUAL BYPASS” THE LOAD IS NOT
PROTECTED AGAINST ANY MAINS FAILURES OR MAINS DISTURBANCES.
6.6.5
Output Switch/Parallel Isolator (IA2)
Every UPS-unit is provided with an output parallel isolator (IA2) which, when opened isolates the
corresponding unit from the PARALLEL BUS and from the LOAD. Once IA2 is open there is no power
on the load coming from the UPS.
In redundant parallel configurations it is used to isolate a unit from the parallel system without the
need of transferring the load to bypass.
POSITION
EFFECT
ON
Normal Operation (Load supplied by UPS)
OFF
UPS isolated from Parallel Bus for maintenance or UPS replacement (UPS not
supplying load)
MAINS
LOAD
MAINTENANCE
BYPASS
UPS
Summary of Contents for Conceptpower DPA 500
Page 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Page 2: ......
Page 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Page 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Page 90: ......
Page 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...