Modbus channel attributes
6.3.2.
Table 6.3.2-1 Modbus channel attributes
Description
Value or Value range/ Default
Name
Data type: Integer
Access: No limitations
The state of the line - whether
it is in use or not. When a line
is not in use, no data can be
transmitted on it, and no data
is received from it. The line
attributes can be read as usual.
Generally, a line must be taken
out of use by setting this attrib-
ute to 0 before the line attrib-
utes can be written. When a
line is stopped by setting the IU
attribute = 0, all data transmis-
sion on the line ceases. How-
ever, before that, the protocol
stack executes to the end all
on-going data transactions. For
example, the polling of the sta-
tion in turn is completed.
0 = Not in use, the line commu-
nication is stopped
1 = In use
Default: 1
In use
Data type: Integer
Access: Read-only
Diagnostic counters(TCP
channel)
The number of transmitted
telegrams.
Transmitted telegrams
Incremented each time a mes-
sage transmission to the Mod-
bus channel fails for some
reason.
Failed transmissions
The number of transmitted
commands.
Transmitted commands
The number of transmitted
replies.
Transmitted replies
Incremented each time the
Modbus OPC Server receives
a message from the Modbus
channel.
Received messages
The number of times there has
been a buffer overflow.
Buffer overflow errors
Number of TCP connection
requests.
TCP connect
Number of accepted TCP con-
nection requests
TCP accept
127
COM600 series 5.0
1MRS758690
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual