Protection activation information (ACT)
5.2.6.
OPC data types
DNP data object
field
Mandat-
ory/Optional
Value/Value range
Type
Name
VT_BOOL
state (0=OFF,
1=ON)
M
BOOLEAN
general
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
phsA
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
phsB
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
phsC
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
neut
VT_14
DNP status
M
Quality
q
VT_Date
<server provided if
none> | Time of
occurrence
M
TimeStamp
t
VT_Date
-
O
Text
Description
d
Directional protection activation information (ACD)
5.2.7.
OPC data types
DNP data object
field
Mandat-
ory/Optional
Value/Value range
Type
Name
VT_BOOL
state (0=OFF,
1=ON)
M
BOOLEAN
general
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
phsA
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
phsB
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
phsC
VT_BOOL
state (0=OFF,
1=ON)
O
BOOLEAN
neut
VT_14
DNP status
M
Quality
q
VT_DATE
<server provided if
none> | Time of
occurrence| MSEC
M
TimeStamp
t
VT_BSTR
-
O
Text
Description
d
104
1MRS758690
COM600 series 5.0
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual