If you clicked Excecute Restoration, you should see load L30201 isolated from
the network in the COM600 HMI, and power restored to load L30202.
Load_restored.PNG
Figure 3.7.3-5 Load restored
Simulating return to normal
3.7.4.
In the restoration mode, if the fault is cleared, you can close the switch powering the
previous fault load. The system will try to return to pre-fault normal mode.
To simulate returning to normal:
1.
In the FDIR Control dialog, select the switch B30201 and click Clear Lockout.
2.
In COM600 HMI, click the switch B30201 and close it by clicking Close and then
Operate in the Switch device control dialog.
You can see the alert icon flashing in the header area.
3.
Click the alert icon.
4.
In the FDIR Mode tab of the FDIR Control dialog, click Return to Normal if it
is valid, or click Cancel.
22
1MRS757279
Grid Automation Controller COM600 4.0
FDIR Operation Manual