![ABB COM600 3.4 User Manual Download Page 64](http://html.mh-extra.com/html/abb/com600-3-4/com600-3-4_user-manual_1209064.webp)
Application layer status codes
5.3.3.
ICCC_INVALID_ATTRIBUTE_VALUE. The value set to an attribute of an IEC
station is incorrect, for example, one of the elements of the vector written to the
SD attribute is out of range.
13851
ICCC_INVALID_INDEX_RANGE. The index range used when accessing an
attribute of an IEC station is incorrect.
13852
ICCC_INVALID_ATTRIBUTE. The STA object attribute used is not valid for the
IEC 60870-5-101 slave protocol.
13853
ICCC_ASDU_TABLE_NOT_CREATED. Internal software error.
13854
ICCC_UNKNOWN_ASDU_NAME. The name of the ASDU written to the SD or
EV attribute is not supported.
13855
ICCC_ASDU_QUEUE_FULL. No more events can be written to one of the queues
by using the SD or EV attribute since the queue is full.
13856
ICCC_MESSAGE_BUFFER_FULL. Internal software error. The value of the ML
attribute may be too small.
13857
ICCC_MESSAGE_FILLING_ERROR. Internal software error. The value of the
ML attribute may be too small.
13858
ICCC_UNKNOWN_ASDU. The number of the ASDU written to the SD or EV
attribute is not supported.
13859
ICCC_NO_ACTIVE_COMMAND. There is no preceding command with the given
address when confirming a command by using the CF attribute. Either the address
is incorrect or the command has not been received.
13860
ICCC_INVALID_QUEUE_NUMBER. The index of the SD or EV attribute is
incorrect.
13861
ICCC_SC_DATA_OVERFLOW. Internal software error.
13862
ICCC_DEVICE_SUSPENDED. The IEC station is in the suspended state. The
reason for this could be that the link is not properly established (for example,
incorrect cable wiring) or the master does not respond.
13863
ICCC_MESSAGE_SENDING_ERROR. Internal software error. This may be the
result of a problem in wiring or hardware.
13864
ICCC_REMOTE_DEVICE_REPLIES_WITH_NACK. The master did not accept
the message but responded with a negative acknowledgment instead. Not used
in the unbalanced mode.
13865
ICCC_LINK_NOT_READY. A message is sent to a line with a non-established
communication.
13866
ICCC_OUT_OF_BUFFERS. Internal software error. Operation could not be
completed since the buffer pool has run out of buffers.
13868
ICCC_DONT_REPLY. Internal software error.
13869
ICCC_DEVICE_STOPPED. The station has been set out of use by using the IU
attribute.
13872
ICCC_NO_ADDRESS_IN_ACP. Internal software error.
13873
ICCC_UNEXPECTED_TYPE_IN_ACP. Internal software error.
13875
64
1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Summary of Contents for COM600 3.4
Page 1: ...Station Automation COM600 3 4 IEC 60870 5 101 Slave OPC User s Manual ...
Page 2: ......
Page 6: ...6 ...
Page 76: ...76 ...
Page 81: ......