Description
Value or Value range/ Default
Property/ Para-
meter
Specifies if the value of indication signal
is sent as double point.
True = 1
False = 0
Send as Double
Point
Specifies the value of indication signal is
sent as inverse value.
True = 1
False = 0
Send as Inverse
Value
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2
Time Tag Handling
Directional protection activation information (ACD)
3.4.5.6.
Table 3.4.5.6-1 Configurable ACD properties for OPC client
Description
Value or Value range/ Default
Property/ Para-
meter
Basic
Common data class according to IEC
61850.
ACD
Common Data
Class
Addresses
IEC address for general indication
0...16777215
General Address
IEC address for neutral
0...16777215
Neutral Address
IEC address for phase A
0...16777215
0 = Not in use
Phase A Address
IEC address for phase B
0...16777215
0 = Not in use
Phase B Address
IEC address for phase C
0...16777215
0 = Not in use
Phase C Address
Common
Class of ASDU. Data sent from the slave
to the master can be assigned to two
classes: class 1 and class 2. Data in class
1 is sent with higher priority than data in
class 2.
1 = Class 1
2 = Class 2
Default: 1 = Class 1
Class
Interrogation group. 1 - 16 general or 1 -
4 counter interrogation.
1...16 (general) or 1...4 (coun-
ters)
Interrogation Group
37
Station Automation COM600 3.4
1MRS755382
IEC 60870-5-101 Slave (OPC) User's Manual