Function blocks
239
1SVC 440 795 M1100
Accuracy
The operating hours counter is accurate to the nearest
minute. If the enable coil signal is terminated within a
minute, the value for seconds is lost.
The value range of the operating hours counter is between 0
hours and 100 years.
PUT, send a value onto the network
The function block allows you to selectively send a 32 bit
value onto the network. The PUT function block provides
data on the CL-NET that another station indicates it requires
via the GET function block.
Figure: 125:
Display system circuit diagram with PUT function
block
Parameter display and parameter set for the PUT function block:
Input
The function block input
>I1
can be assigned the following
operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
– IA01: Terminal I7
– IA02: Terminal I8
– IA03: Terminal I11
– IA04: Terminal I12
• Analog output QA01
• Actual value …QV> of another function block
T 01Q1---------------------------Ä PT16T
PT16Q1---------------------------Ä C 01C
PT01 11
-
>I1
PT01
PUT function block (places a value onto the network),
number 11
-
Does not appear in the parameter display
>I1
Setpoint value which is put onto the CL-NET network