10 CDPI-01 communication adapter module
Connecting the panel cabling to the drive
Alternative 1: Routing the cabling inside the drive
If you have several drives on the panel bus, repeat these steps in
all drives.
1. Stop the drive and disconnect it from the power line. Wait for 5
minutes to let the intermediate circuit capacitors discharge
before you continue.
2. Remove the drive cover.
3. Use a multimeter to make sure that there are no parts under
voltage in reach.
4. Cut an adequate hole into the rubber grommet. Slide the
grommet onto the cable. Slide the cable through the hole of the
bottom plate and attach the grommet to the hole.
5. Route the cable first under the cable clamp (a) and then
anticlockwise round the panel housing (b).
6. Connect the panel cable to module connector X101.
For an illustration, see page
.
7. If you need to chain the panel bus to another drive:
•
repeat steps 4...5 for the chaining cable,
•
and connect the chaining cable to module connector X102.