background image

Options for ABB drives, converters and inverters

Quick guide

CCA-01 communication adapter

CCA-01 communication adapter provides serial communication interface to
certain unpowered ABB drives frequency converters.

Safety instructions

Obey these safety instructions when using the communication adapter.

WARNING!

 Ignoring the following instructions can cause physical

injury or death or damage to the equipment.

Use the communication adapter only with an unpowered drive.

General

CCA-01 communication adapter provides safety isolation of both serial communication and control
board power supply. The power supply is taken from the USB port of a PC. The adapter can be used
with several ABB drives PC tools: software loading tools and commissioning tools.

USB cable

Use only the supplied USB cable. Connect both USB connectors to the PC to ensure sufficient
current supply to the adapter and drive control board.

USB drivers

The adapter uses the same USB drivers as ACS-AP-x control panel. See

Drive composer start-up

and maintenance PC tool user's manual

 [3AUA0000094606 (English)] for installation instructions.

Indicator LEDs

LED indications

System state / explanation

COMM

 (CCA-01 to drive communication)

Off

No communication

Blinking orange

Communication between PC tool and drive

DRIVE

 (drive power supply indication)

Off

Drive connected, but CCA-01 powering not succeeded

Blinking green

No drive connected (ready for connection)

Green

Drive connected

Red

Drive power supply is connected

POWER

 (CCA-01 USB power supply indication)

Off

Not powered

Green

CCA-01 is powered from USB

Blinking red

CCA-01 is in fault state