OPERATING LEVEL
6.1.3
View Divert Parameters
The View Divert Parameters Page displays parameters and messages set up in the Divert Page shown in Section 7.1.5
.
These
parameters can be monitored but not modified at this level.
Dual
RT
rt-dU.t
----
dIVErt
PAGE
2nd-rt
----
rt-dEV
----
d-OdE
-ULtI
SINGLE
dIVErt
----
Single
Divert
Multi
Divert
HYSt
----
t-HYSt
----
HOt-1
----
Multi
Divert
dVrt-2
----
HOt-2
----
dVrt-1
----
Single
Divert
To Top
of Page
dVrt-8
HOt-8
To Top
of Page
Single
RT
Page Header –
Divert Page
Second RT Value
If dual RTD values are selected, the temperature value for the second RTD is displayed.
RT Deviation Trip Value
Displays the deviation level (1
st
– 2
nd
RTD value) set for difference condition.
If (1
st
– 2
nd
RTD) >
rt–deV
then deviation trip condition is true.
RT Divert
Shows if diversion enabled for the above trip condition.
Divert Mode
Displays the divert mode configured (multi or single):
MULtI
–
Up to eight divert set points,
SINGLE
–
One divert set point.
Divert Number
Displays the number of the divert set point(s): 1, 2, 3, 4, 5, 6, 7 or 8 (used with associated
Divert
Set Point and Hot Water Set Temperature
displays) – models 1952 and 1953 only.
Caution.
Do not change divert numbers during a process (only before or after).
Divert Set Point 1
Displays the temperature set for divert set point 1.
Divert Hysteresis Point
Displays the hysteresis value set (in engineering units) common to all set points.
Note.
Only activated on values above the divert set point temperature.
Time Hysteresis
Displays the time hysteresis value set between 0 and 9999 seconds (common to all set points).
Note.
If product temperature reaches the set point value, forward flow is initiated
t-hyst
seconds after reaching this value. If the temperature drops below the setting in the
Divert Set Point
display, flow is diverted immediately.
Hot Water Set Temperature 1
(Models 1952 and 1953 only)
Displays the hot water control temperature set point for divert set point 1, used in conjunction with
associated divert number 1.
Divert Set Points 2 to 8
Displays the temperature for divert set points (from 2 to 8 as selected) used in conjunction with
associated divert numbers 2 to 8.
Hot Water Set Temperature 2
(Models 1952 and 1953 only)
Displays the hot water control temperature set point for divert set points (from 2 to 8 as selected)
used in conjunction with associated divert numbers 2 to 8.