background image

ABB INDUSTRIAL DRIVES

BAMU-12C auxiliary measurement unit

Hardware manual

Summary of Contents for BAMU-12C

Page 1: ... ABB INDUSTRIAL DRIVES BAMU 12C auxiliary measurement unit Hardware manual ...

Page 2: ......

Page 3: ...BAMU 12C auxiliary measurement unit Hardware manual Table of contents 3 Installation 2020 ABB Oy All Rights Reserved 3AXD50000117840 Rev B EN EFFECTIVE 2020 01 29 ...

Page 4: ......

Page 5: ...ical installation 17 Electrical installation 17 Connection diagram 18 Voltage measurement connections XU1 XU2 19 Current measurement connections XIU XIV XIW 19 Power supply connection XPOW 19 Communication link connection V30 19 Connection to BCU control unit 20 Wiring example Voltage and current measurements in use 21 Wiring example Voltage measurement in weak network 22 Wiring example DC DC conv...

Page 6: ...6 ...

Page 7: ...are manual For the safety instructions of air cooled units see ACS880 multidrive cabinets and modules safety instructions 3AUA0000102301 English For the safety instructions of liquid cooled units see Safety instructions for ACS880 liquid cooled multidrive cabinets and modules 3AXD50000048633 English WARNING Note that BAMU 12C auxiliary measurement unit is used for measuring main circuit voltage Ma...

Page 8: ...ns 3AXD50000048635 ACS880 liquid cooled multidrive cabinets mechanical installation instructions 3AXD50000126880 CIO 01 I O module for distributed I O bus control user s manual Supply unit manuals 3AUA0000130644 ACS880 207 IGBT supply units hardware manual 3AXD50000174782 ACS880 207LC IGBT supply units hardware manual 3AUA0000131562 ACS880 IGBT supply control program firmware manual 3AUA0000102453...

Page 9: ...lanning instructions 3AUA0000107668 Drive modules cabinet design and construction instructions 3AUA0000113605 BCU 02 12 22 control units hardware manual 3AXD50000126880 CIO 01 I O module for distributed I O bus control user s manual Supply module manuals 3AUA0000131525 ACS880 204 IGBT supply modules hardware manual 3AXD50000284436 ACS880 204LC IGBT supply modules hardware manual 3AUA0000131562 ACS...

Page 10: ...s 3AXD50000129607 ACS880 1007LC liquid cooling unit user s manual 3AUA0000085685 ACX AP x assistant control panels user s manual 3AXD50000117840 BAMU 12C auxiliary measurement unit hardware manual 3AUA0000094606 Drive composer start up and maintenance PC tool user s manual 3AUA0000127808 Drive application programming IEC 61131 3 manual 3AXD50000010531 Installation frames for ACS880 multidrive modu...

Page 11: ...ge inputs three current inputs indication LEDs 24 V DC supply voltage optical link for communication with the overriding drive control unit Compatibility The measuring unit is compatible with BCU 02 12 and 22 control units The control unit must also be equipped with a control program that can communicate with the measuring unit for example the IGBT supply control program For the compatibility with...

Page 12: ...Layout drawing The following figure shows the layout of the measurement unit 12 Hardware description ...

Page 13: ... 19 XIV Current measurement connector For pin descriptions see section Current measurement connections XIU XIV XIW page 19 XIW Fiber optic connector V1R Fiber optic connector V1T Power supply connector For pin descriptions see section Power supply connection XPOW page 19 XPOW LEDs Description Color LED Power on Green POWER Fiber optic link fault Red LINK FAULT Input U2 voltage exceeds 60 V Yellow ...

Page 14: ...14 ...

Page 15: ... the immediate vicinity of electromagnetic disturbance sources such as relays contactors brake choppers power and motor cabling The minimum recommended distance from such components is 200 mm 7 9 in We recommend to install metallic screening between the measurement unit and the source of disturbance This can reduce the required distance Mount the control unit so that air can pass freely through th...

Page 16: ...l to the cabinet into which the unit is to be installed 2 Fasten the two latches to the back of the measurement unit with four screws 3 Click the measurement unit to the rail as shown below 4 Make sure that the installation rail is grounded properly either via the assembly plate or with a separate grounding wire The unit is grounded through the rail 2 2 3 16 Installation ...

Page 17: ...surement 1 3 S3 V phase current input 4 S4 V phase current output XIW Current measurement 1 5 S5 W phase current input 6 S6 W phase current output XU1 Voltage measurement 2 1 U1 U phase voltage 1 2 Not connected 3 V1 V phase voltage 1 4 Not connected 5 W1 W phase voltage 1 6 Not connected 7 N1 Neutral 1 XU2 Voltage measurement 2 1 U2 U phase voltage 2 2 Not connected 3 V2 V phase voltage 2 4 Not c...

Page 18: ...ected 4 W phase 1 W1 5 Not connected 6 Neutral 1 N1 7 Pin descriptions of connector XU2 are given in the table below Description Name Pin U phase 2 U2 1 Not connected 2 V phase 2 V2 3 Not connected 4 W phase 2 W2 5 Not connected 6 Neutral 2 N2 7 Use cable rated for the measured voltage Recommended conductor cross section is 1 2 5 mm2 Tightening torque 0 5 0 6 N m 18 Installation ...

Page 19: ...ng torque 0 5 0 6 N m Note In current measurements make sure that the current transformers are wired in the correct direction see wiring example on page 20 Power supply connection XPOW Pin descriptions of power supply connector are given in the table below Description Direction Name Pin 24 V DC supply voltage In 24V 1 DC neutral In 0V 2 Ground In GND_S 3 Recommended conductor cross section is 1 2 ...

Page 20: ...2 1 S1 S2 P1 P2 B2 2 S1 S2 XIU 2 11H XIV 4 XIW 6 XIW 5 11H XIV 3 XIU 1 SEE NOTE BELOW NOTE CURRENT TRANSFORMER CIRCUIT WIRING WITH INSULATION HOSE IH NOTE THE TWISTING OF CONDUCTORS 001 002 ISU I ACS880 207 1050A 7 690V 50 Hz IP22 Circuit diagram EFS2 EN 9 1 2020 Generated by ADG2 ABB Drives PSL2 50Mb U1 V1 W1 N1 U2 V2 W2 IU IV IW IN OUT IN OUT IN OUT 0V GND_S 24V F1 1A N2 A2 XU1 1 XPOW 3 XPOW 2 X...

Page 21: ...3 14 21 22 R4 3 1 2 R4 2 1 2 R4 1 1 2 F1 1 1 2 F1 2 1 2 F1 3 1 2 Q1W1 1 F5 2 12F F5 4 F5 6 001 002 ISU I ACS880 207 1050A 7 690V 50 Hz IP22 Circuit diagram EFS2 EN 9 1 2020 Generated by ADG2 ABB Drives PSL2 50Mb U1 V1 W1 N1 U2 V2 W2 IU IV IW IN OUT IN OUT IN OUT 0V GND_S 24V F1 1A N2 A2 XU1 1 XPOW 3 XPOW 2 XPOW 1 V30 V1R V30 V1T XIW 6 XIW 5 XIV 4 XIV 3 XIU 2 XIU 1 BAMU 12C Auxiliary Measuring Unit...

Page 22: ...W 1 V30 V1R V30 V1T XIW 6 XIW 5 XIV 4 XIV 3 XIU 2 XIU 1 BAMU 12C Auxiliary Measuring Unit XU1 3 XU1 4 XU1 5 XU1 6 XU1 7 XU2 1 XU2 2 XU2 3 XU2 4 XU2 5 XU2 6 XU2 7 PWR OK GREEN LINK FAULT RED U2 60V GREEN U1 60V GREEN XU1 2 ESM 1 ESM 1 1PE 7PE 2 012 020 Circuit diagram EFS2 EN 9 1 2020 Generated by ADG2 ABB Drives BCU CONTROL UNIT POWER 24V 22 Installation ...

Page 23: ...Technical data Contents of this chapter The chapter contains the technical data of BAMU 12C auxiliary measurement unit 4 Technical data 23 ...

Page 24: ...Dimension drawing Dimensions in mm 1 mm 0 0394 in 24 Technical data ...

Page 25: ...rage temperature 40 85 C 40 185 F Maximum relative humidity 90 non condensing Maximum operating altitude 4000 m 13123 ft Voltage measurement specification Two identical independent measurements channels Both channels include three phase voltage inputs and neutral input U1 V1 W1 N1 and U2 V2 W2 N2 Number 2 0 kV peak phase to phase Maximum voltage connected to the voltage measurement terminals is 60...

Page 26: ...ions IEC 61800 5 1 Semiconductor power converters for adjustable frequency drive systems UL 508 C Industrial Control Equipment EMC emission EN IEC 6100 6 4 2007 Emission standard for industrial environments EMC immunity EN IEC 61000 6 2 2005 Immunity for industrial environments 26 Technical data ...

Page 27: ... by navigating to www abb com searchchannels Product training For information on ABB product training navigate to new abb com service training Providing feedback on ABB manuals Your comments on our manuals are welcome Navigate to new abb com drives manuals feedback form Document library on the Internet You can find manuals and other product documents in PDF format on the Internet at www abb com dr...

Page 28: ...www abb com drives 3AXD50000117840B 2020 ABB Oy All Rights Reserved Specifications subject to change without notice 3AXD50000117840 Rev B EN EFFECTIVE 2020 01 29 ...